BLACK CORE黑核工业
Menu
EN
Send Inquiry

CQC · COMPLIANCE

Certification & Compliance

CQC certification and type-test information, organized by product and documentation scope.

01 — CQC

CQC Product Certification

CQC certification and type-test information, organized by product and documentation scope.

CQC Product Certification

RFM1-125 Series

Certificate NumberCQC22107358419
Test Report No.19101-DWRY220493
ManufacturerSuzhou Dongge Power Technology Co., Ltd.
Product NameMolded Case Circuit Breaker
Document CoverageRFM1-125 series including 1P / 2P / 3P / 4P
Applicable StandardGB/T 14048.2-2020
Rated Operational Voltage UeAC400V
Rated Current Range40A–125A
Rated Service Short-Circuit Breaking Capacity Ics35kA
Rated Ultimate Short-Circuit Breaking Capacity Icu55kA
Pole Coverage1P / 2P / 3P / 4P
Certification Validity2022-09-13 to 2032-09-12
CQC Product Certification

RFM1-250L Series

Certificate NumberCQC22107358969
Test Report No.19101-DWRY220494
ManufacturerSuzhou Dongge Power Technology Co., Ltd.
Product NameMolded Case Circuit Breaker
Document CoverageRFM1-250L/M series including 1P / 2P / 3P / 4P
Applicable StandardGB/T 14048.2-2020
Rated Operational Voltage UeAC400V
Rated Current Range125A–250A
Breaking ClassL Type
Rated Service Short-Circuit Breaking Capacity Ics10kA
Rated Ultimate Short-Circuit Breaking Capacity Icu15kA
Pole Coverage1P / 2P / 3P / 4P
Certification Validity2022-09-13 to 2032-09-12
RFM1-400 Series CQC Reference Documentation

RFM1-400 Series

The available report covers RFM1-400 3P / 4P configurations only. It does not establish certification or test coverage for RFM1-400L / 1P.

Certificate NumberCQC22107358650
Test Report No.19101-DWRY220489
ManufacturerSuzhou Dongge Power Technology Co., Ltd.
Document Coverage3P / 4P Series Reference
Certification Validity2022-09-13 to 2032-09-12

02 — TYPE TEST

English Test Report Summary

Model-specific engineering and compliance resources.

English Test Report Summary

RFM1-125 / 1P

Product Name
Molded Case Circuit Breaker
Test Report No.
19101-DWRY220493
Manufacturer
Suzhou Dongge Power Technology Co., Ltd.
Testing Laboratory
Wenzhou Customs Comprehensive Technical Service Center / National Key Laboratory of Low Voltage Electrical Apparatus Testing
Standard
GB/T 14048.2-2020
Model Series
RFM1-125 / 1P
Rated Current
40A / 50A / 63A / 80A / 100A / 125A
Rated Operational Voltage Ue
AC400V
Rated Insulation Voltage Ui
1000V
Rated Impulse Withstand Voltage Uimp
8kV
Rated Service Short-Circuit Breaking Capacity Ics
35kA
Rated Ultimate Short-Circuit Breaking Capacity Icu
55kA
Trip Unit
Thermal-Magnetic
Main Test Items
Rated parameters, thermal-magnetic trip performance, isolation function and short-circuit breaking performance.
Test Conclusion
Passed according to GB/T 14048.2-2020.
Download English Test Report Summary Download Original Chinese Test Report
English Test Report Summary

RFM1-250L / 1P

Product Name
Molded Case Circuit Breaker
Test Report No.
19101-DWRY220494
Manufacturer
Suzhou Dongge Power Technology Co., Ltd.
Testing Laboratory
Wenzhou Customs Comprehensive Technical Service Center / National Key Laboratory of Low Voltage Electrical Apparatus Testing
Standard
GB/T 14048.2-2020
Model Series
RFM1-250L / 1P
Rated Current
125A / 140A / 160A / 180A / 200A / 225A / 250A
Rated Operational Voltage Ue
AC400V
Rated Insulation Voltage Ui
1000V
Rated Impulse Withstand Voltage Uimp
8kV
Rated Service Short-Circuit Breaking Capacity Ics
10kA
Rated Ultimate Short-Circuit Breaking Capacity Icu
15kA
Trip Unit
Thermal-Magnetic
Main Test Items
Rated parameters, thermal-magnetic trip performance, isolation function and short-circuit breaking performance.
Test Conclusion
Passed according to GB/T 14048.2-2020.
Download English Test Report Summary Download Original Chinese Test Report
RFM1-400 Series Test Report

RFM1-400 / 3300 / 4300 (3P / 4P)

RFM1-400 Series Reference Data The available report covers RFM1-400 3P / 4P configurations only. It does not establish certification or test coverage for RFM1-400L / 1P.

Product Name
Molded Case Circuit Breaker
Test Report No.
19101-DWRY220489
Manufacturer
Suzhou Dongge Power Technology Co., Ltd.
Testing Laboratory
Wenzhou Customs Comprehensive Technical Service Center / National Key Laboratory of Low Voltage Electrical Apparatus Testing
Standard
GB/T 14048.2-2020
Model Series
RFM1-400 / 3300 / 4300 (3P / 4P)
Rated Current
250A / 315A / 350A / 400A
Rated Operational Voltage Ue
AC400V
Rated Insulation Voltage Ui
1000V
Rated Impulse Withstand Voltage Uimp
8kV
Rated Service Short-Circuit Breaking Capacity Ics
50kA
Rated Ultimate Short-Circuit Breaking Capacity Icu
65kA
Trip Unit
Thermal-Magnetic
Main Test Items
Rated parameters, thermal-magnetic trip performance, isolation function and short-circuit breaking performance.
Test Conclusion
Passed according to GB/T 14048.2-2020.
Download English Test Report Summary Download Original Chinese Test Report